2022-10-04 10:32:20FIRE REVIEW COMMENTS:
  
 PROVIDE CLARIFICATION AS TO MANUAL PULL STATION
 LOCATIONS. MANUAL ALARM BOXES SHALL BE LOCATED WITHIN
 5??? OF EACH EXIT DOORWAY. SOME MARKED EXITS DID NOT
 INDICATE A MANUAL PULL STATION AND THE DISTANCE FROM
 THE EXIT TO THE MANUAL STATION WAS NOT IDENTIFIED. NFPA
 72, 17.14.8.4
  
 PROVIDE A CLARIFICATION OF VISIBLE SIGNALING DEVICE
 LOCATIONS FOR ALL OCCUPIABLE SPACES, SUCH AS THE
 WALK-INS. NFPA 72, 18.5.1.2
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  