| Plan Review Notes For Permit 22091286 |
| Permit Number |
22091286 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-04 10:32:20 | FIRE REVIEW COMMENTS: | | | | | | PROVIDE CLARIFICATION AS TO MANUAL PULL STATION | | | LOCATIONS. MANUAL ALARM BOXES SHALL BE LOCATED WITHIN | | | 5??? OF EACH EXIT DOORWAY. SOME MARKED EXITS DID NOT | | | INDICATE A MANUAL PULL STATION AND THE DISTANCE FROM | | | THE EXIT TO THE MANUAL STATION WAS NOT IDENTIFIED. NFPA | | | 72, 17.14.8.4 | | | | | | PROVIDE A CLARIFICATION OF VISIBLE SIGNALING DEVICE | | | LOCATIONS FOR ALL OCCUPIABLE SPACES, SUCH AS THE | | | WALK-INS. NFPA 72, 18.5.1.2 | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|