| 2023-04-19 08:57:13 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE ADDITIONAL DETAILS FOR THE "THREADED |
| | BEAM" AT THE REAR PATIO - SHOW ATTACHMENTS TO THE |
| | STRUCTURE. FBC 107.2.1 |
| | |
| | 2) IN THE PRODUCT APPROVAL FOR THE ROOF TILE - PLEASE |
| | CIRCLE THE ROOF TILE ATTACHMENTS TO BE USED - IF USING |
| | ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL. |
| | FBC WPB 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE |
| | CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, |
| | DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM, |
| | MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| | REQUIRED TO BE |
| | INSTALLED |
| | |
| | 3) PLEASE PRIVIDE THE FLAME CERTIFICATION (ICC |
| | EVALUATION REPORT) FOR THE FOAM INSULATION AT THE |
| | BOTTOM OF THE ROOF DECK - R316.3 SURFACE BURNING |
| | CHARACTERISTICS. |
| | UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM |
| | PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN |
| | MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION |
| | SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND |
| | SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450 |
| | WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY |
| | INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723. |
| | |
| | 4) THE SOIL REPORT DOES NOT SHOW AS DIGITALLY SIGNED IN |
| | ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX |
| | NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED |
| | IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |
| | |
| | |