2022-10-05 11:27:561ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND - 107.3.5 - THE SPEC SHEET FOR THE
 BACKFLOW DEVICE TO BE INSTALLED NEEDS TO INDICATE IT IS
 LEAD FREE. BE SURE TO HIGHLIGHT THE MAKE, MODEL, AND
 SIZE OF THE DEVICE. THE ONLY MARKING ON THE SPEC SHEET
 THAT I CAN THINK MIGHT INDICATE "LEAD FREE" IS THE UL
 MARKING WITH "3/4" -2" UNDERNEATH THE UL. IF THAT IS
 THE INDICATOR, PLEASE SEND ME SOMETHING THAT CLEARY
 DEFINES THAT MARKING. OTHERWISE, YOU WILL NEED TO
 PROVIDE A SPEC SHEET THAT CLEALY SAYS "LEAD FREE".
  
 2. 2017 WPB AMEND - 107.3.5 - PLEASE PROVIDE A BASIC
 SITE PLAN SHOWING THE LOCATION OF THE BACKFLOW
 PREVENTER
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  