Plan Review Notes
Plan Review Notes For Permit 22091262
Permit Number 22091262
Review Stop B
Sequence Number 1
Notes
Date Text
2022-11-04 13:25:241ST BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, CBO, BN, PX, CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: EVERY STRUCTURE SUBJECT TO WIND LOADS SHALL BE
 DESIGNED PER FBC CHPT 16, FBC RES CHPT 3 SECTION R301
 OR ASCE 7.
  
 1.PROVIDE A COPY OF THE MOST RECENT BOUNDARY LINE
 SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2.PROVIDE THE MANUFACTURER???S CERTIFICATION UNDER THE
 MANUFACTURED BUILDING PROGRAM, AS PROVIDED FOR UNDER
 CHAPTER 553, PART 1, FLORIDA STATUTES. (F.S.)
 INCLUDE A COPY OF THE CURRENT FLORIDA PRODUCT APPROVAL.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 OPTION TO #2 ABOVE:
  
 3. PROVIDE THE FOLLOWING BUILDING PLANS AND DETAILS
 3A) FOUNDATION PROVIDE POST BASE CONNECTOR
 3B) WALL PROVIDE POSTL TO TRUSS CONNECTOR.
 3C) ROOF PROVIDE TRELLIS TO TRUSS CONNECTOR.
 3D) PROVIDE A FASTENER SCHEDULE OR SPECIFY WHAT
 FASTENERS ARE USED FOR EACH CONNECTOR.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  