| 2023-01-26 16:42:17 | 2ND REVIEW FMC |
| | PERMIT: 22091257 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THIS REVIEWER DID NOT COMMENT THAT THE SMOKER HAD TO |
| | BE UL LISTED. THE CODE STATES THAT IT SHOULD BE LISTED |
| | AND LABELED. IT CAN BE FROM ANOTHER TESTING FACILITY. |
| | AGAIN, I ASK THAT YOU SUBMIT THE SMOKER???S |
| | SPECIFICATIONS AND INSTALLATION INSTRUCTIONS AS THE |
| | SMOKERS EXHAUST AND COMBUSTION AIR WILL HAVE AN EFFECT |
| | ON THE MECHANICAL SYSTEM DESIGN. THE MANUFACTURER OF |
| | THIS SMOKER SHOULD STATE THE COMBUSTION AIR AMOUNTS |
| | WILL BE NEEDED. FMC 917.1 |
| | |
| | 2) THIS SMOKER MUST ALSO MEET ALL OF THE REQUIREMENTS |
| | OF FMC 906. PROVIDE A COMPLETE DESIGN FOR THIS SMOKER |
| | THAT INCLUDES CHAPTERS 3,5,7 AND 8. |
| | |
| | 3) IS THERE TO BE ANY OTHER COOKING IN THIS KITCHEN? |
| | PROVIDE A LIST OR MENU FOR THE FOODS SERVED IN THIS |
| | RESTAURANT. |
| | |
| | 4) AGAIN, PROVIDE THE USE OF SPACE FOR THE ADJACENT |
| | TENANT SPACE. WHAT WAS THE PREVIOUS USE OF THIS SPACE? |
| | PROVIDE THE SQUARE FOOTAGE OF THIS SPACE. FBC 107.3.5 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |