| 2022-11-01 13:34:20 | 1ST REVIEW FMC |
| | PERMIT: 22100465 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE REVISE THE ADDRESS ON THE DRAWINGS TO THE |
| | CORRECTED ADDRESS: 206 S. OLIVE. |
| | |
| | 2) PROVIDE A SITE PLAN FOR THIS BUILDING THAT INCLUDES |
| | THE PROPERTY LOT LINES. |
| | |
| | 3) PROVIDE A DETAIL OF THE GREASE DUCT AND HEAT PIPE |
| | THAT IS EXISTING INCLUDING THE TERMINATION LOCATIONS. |
| | FBC107.3.5 |
| | |
| | 4) PLEASE ADD A NOTE ON THE MECHANICAL DRAWING STATING |
| | THAT THE KITCHEN HOOD, GREASE DUCT AND WALK-IN COOLERS |
| | WILL REQUIRE SEPARATE PERMIT APPLICATIONS AND |
| | MECHANICAL REVIEWS AS THEY WILL NOT BE REVIEWED UNDER |
| | THIS PERMIT. |
| | |
| | 5) PROVIDE DETAILS FOR THE SMOKER. FMC 906 |
| | |
| | 6) THE COOKING EQUIPMENT INCLUDING THE SMOKER SHALL BE |
| | LISTED AND LABELED FOR INDOOR USE. FMC 917.1 |
| | |
| | 7) PROVIDE DETAILS AS TO WHAT WILL BE UNDER THE HEAT |
| | HOOD. SHEET 4.0M INDICATES EXISTING WELDED DUCTWORK TO |
| | ROOF. SHEET 1.1A DEMO DRAWING DOES NOT SHOW THIS DUCT |
| | WORK AS EXISTING. PLEASE CORRECT THE STATEMENT ON 4.0M |
| | TO INDICATE THIS TO BE A NEW HEAT DUCT. FBC 107.3.5 |
| | |
| | 8) PLEASE CORRECT THE OUTDOOR AIR CALCULATIONS. DINING |
| | ROOM OUTDOOR AIR RATE FOR CFM/FT2 SHOULD BE CALCULATED |
| | AT .18 NOT .12. THIS WOULD MAKE THE TOTAL OUTDOOR AIR |
| | FOR THIS AREA TO BE 261 CFM???S. FMC TABLE 403.3.1.1 |
| | |
| | 9) THE OUTDOOR AIR CALCULATIONS FOR THE KITCHEN SHOULD |
| | SHOW 79 CFM???S OF OUTDOOR AIR REQUIRED WITH 197 |
| | CFM???S OF REQUIRED EXHAUST FOR THIS KITCHEN. FMC TABLE |
| | 403.3.1.1 |
| | |
| | 10) PLEASE PROVIDE THE AIR BALANCE DESIGN FOR THIS |
| | TENANT SPACE. FMC 508.1.2 |
| | |
| | 11) THE NEW FLOOR PLAN ON 1.1A INDICATES A NEW WALL |
| | OPENING INTO THE TENANT SPACE BESIDE OF THIS TENANT. |
| | PROVIDE THE OCCUPANCY AND USE OF SPACE FOR THIS TENANT |
| | SPACE ALONG WITH THE MECHANICAL SYSTEM SIZING. FMC |
| | 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |