| 2022-10-22 16:08:16 | [email protected] | | | [email protected] | | | | | | 1. FBC 22527-R9, SHEET 4 OF 18, HAS DOOR APPLICATION | | | MARKED WHICH DOES NOT MEET ENGINEERS CALCULATED DESIGN | | | PRESSURE REQUIREMENTS. PLEASE CLARIFY AND RESUBMIT. FBC | | | 107.2 | | | 2. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO | | | THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR | | | FBC B 1405.4. | | | |
|