| 2023-07-11 10:27:59 | 3RD PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.2.1 - THE INFORMATION ON THE |
| | PERMIT DOCUMENTS SHOULD BE CLEAR IN ORDER TO REVIEW FOR |
| | CODE COMPLIANCE. YOU ARE LABELING SINKS THAT SHOULD BE |
| | LABELED AS LAVATORIES. YOU HAVE LABELED "LAV" AS WHAT |
| | SHOULD BE A SHOWER AND A TUB IN THE MASTER BATH. THE |
| | "LAV" IN THE 2ND BEDROOM BATH IS ACTUALLY A TUB, AND |
| | THE SINK SHOULD BE LABELED AS A LAV. "SINKS" ARE NOT |
| | ALLOWED TO SERVE AS WET VENTS. AND, THE OFFICE BATHROOM |
| | HAS A SHOWER LABELED AS A "LAV". PLEASE APPROPRIATELY |
| | LABEL THE FIXTURES. |
| | |
| | 2. 2020 FRC P3101.2.1 - THE WATER CLOSET IN THE HALL |
| | BATH IS NOT VENTED TO CODE. THE FIXTURE DRAIN OF THE |
| | WATER CLOSET CANNOT CONNECT TO THE HORIZONTAL BRANCH |
| | SYSTEM WITHOUT A VENT. IT MUST CONNECT TO THE WET VENT |
| | SYSTEM OR HAVE ITS OWN VENT. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - THE "SINK" NEXT TO THE |
| | AUTOMATIC CLOTHES WASHER IS NOT DRAWN ON THE ISOMETRIC |
| | DRAWING. |
| | |
| | PLEASE APPROPRIATELY LABEL THE FIXTURES AND RESUMBIT A |
| | CODE COMPLIANT ISOMETRIC OF THE DWV SYSTEM. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |