2023-07-11 10:27:593RD PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - THE INFORMATION ON THE
 PERMIT DOCUMENTS SHOULD BE CLEAR IN ORDER TO REVIEW FOR
 CODE COMPLIANCE. YOU ARE LABELING SINKS THAT SHOULD BE
 LABELED AS LAVATORIES. YOU HAVE LABELED "LAV" AS WHAT
 SHOULD BE A SHOWER AND A TUB IN THE MASTER BATH. THE
 "LAV" IN THE 2ND BEDROOM BATH IS ACTUALLY A TUB, AND
 THE SINK SHOULD BE LABELED AS A LAV. "SINKS" ARE NOT
 ALLOWED TO SERVE AS WET VENTS. AND, THE OFFICE BATHROOM
 HAS A SHOWER LABELED AS A "LAV". PLEASE APPROPRIATELY
 LABEL THE FIXTURES.
  
 2. 2020 FRC P3101.2.1 - THE WATER CLOSET IN THE HALL
 BATH IS NOT VENTED TO CODE. THE FIXTURE DRAIN OF THE
 WATER CLOSET CANNOT CONNECT TO THE HORIZONTAL BRANCH
 SYSTEM WITHOUT A VENT. IT MUST CONNECT TO THE WET VENT
 SYSTEM OR HAVE ITS OWN VENT.
  
 3. 2017 WPB AMENDS 107.2.1 - THE "SINK" NEXT TO THE
 AUTOMATIC CLOTHES WASHER IS NOT DRAWN ON THE ISOMETRIC
 DRAWING.
  
 PLEASE APPROPRIATELY LABEL THE FIXTURES AND RESUMBIT A
 CODE COMPLIANT ISOMETRIC OF THE DWV SYSTEM.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved