| Plan Review Notes For Permit 22091246 |
| Permit Number |
22091246 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-26 12:57:11 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22091246 | | | 10/26/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P-1: THE MEN'S AND WOMEN'S TOILET ROOM DOORS | | | SHALL NOT SWING INTO THE CLEAR FLOOR SPACES FOR THE | | | LAVATORIES- SEC. 603.2.3 FBC ACC. PLEASE SEE EXCEPTION | | | 2 FOR ADDITIONAL INFORMATION. | | | | | | 2) P-1: THE 1/2--INCH HW SUPPLY PIPES TO THE NEW | | | LAVATORIES ARE EXCEEDING THEIR MAXIMUM ALLOWABLE 2-FT. | | | LENGTHS PER TABLE C404.5.1 FBC EC. | | | | | | 3) P-1: PLEASE CORRECT WATER RISER NOTE # SPECIFYING | | | 5/8-INCH HW PIPE INSULATION. REFER TO TABLE C403.2.10 | | | FBC EC- MINIMUM 1-INCH THICK INSULATION REQUIRED. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|