| 2022-10-20 13:39:28 | ELECTRIC REVIEW FAILED |
| | 1) ELECTRICAL DRAWINGS APPEAR TO BE PREPARED BY THE |
| | GENERAL CONTRACTOR. PLEASE DETAIL UNDER WHAT STATUTE |
| | THIS IS STATUTE COMPLIANT AND DOES NOT REQUIRE |
| | PROFESSIONAL ENGINEERED DRAWINGS. IN ADDITION THIS |
| | DRAWING STATES NO FIRE ALARM WORK IS TO BE DONE, |
| | HOWEVER, IT IS NOT DETAILED HOW THE REPLACED DAMPER IN |
| | THE EQUIPMENT ROOM IS CONTROLLED. IF IT IS VIA THE FIRE |
| | ALARM THEN THIS SHOULD BE STATED AND MAY ALSO REQUIRE |
| | PROFESSIONAL ENGINEER. FSS 471.003 FSS 489 |
| | 2 PLANS DO NOT DETAIL VOLTAGES OR SPECS OF CONTROLLER |
| | AND ATS DISCONNECTS. IF ANY 480 VOLT WORK IS TO BE |
| | DONE, THEN, PLEASE CLARIFY HOW PREPARED DRAWINGS COMPLY |
| | WITH FS 471.003 (H) 2(A) |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |