Plan Review Notes
Plan Review Notes For Permit 22091180
Permit Number 22091180
Review Stop G
Sequence Number 2
Notes
Date Text
2022-10-24 07:50:222ND GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - IT IS NOT CLEAR WHERE THE
 DRYER IS. THERE IS A GAS DETAIL THAT SHOWS 1" PE GOING
 TO A DRYER BUT THE DRYER IS NOT ON THE FLOOR PLAN.
 CLARIFY.
  
 2. 2020 FRC G2439.5 (614.6) WHEN DETAILING THE DRYER,
 PLEASE SHOW MAKEUP AIR FOR DRYER. PLEASE SHOW THE
 CALCULATION FOR THE REQUIREMENT OR EXCEPTION TO THE
 NEED FOR MAKE-UP AIR FOR THE DRYER.
  
 3. 2020 FRC G2415.17.1 (404.17.1) WHEN DETAILING THE
 GAS LINE TO THE DRYER, PLEASE NOT THAT PLASTIC GAS LINE
 SHALL BE INSTALLED OUTDOORS UNDERGROUND ONLY. IT SHALL
 NOT BE USED WITHIN OR UNDER ANY BUILDING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  