| Plan Review Notes For Permit 22091180 |
| Permit Number |
22091180 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-17 09:04:51 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMENDS 107.2.1 - PLEASE DETAIL WHERE THE | | | WASHER IS. THE ISOMETRIC SHOWS A WATER LINE TO THE | | | WASHER BUT IT IS NOT LOCATED ON THE FLOOR PLAN. CLARIFY | | | PLEASE. | | | | | | 2. 2020 FRC P2906.5 - PLEASE NOTE THAT WHEN DETAILING | | | THE WASHING MACHINE, THAT PVC PIPE IS NOT ALLOWED | | | WITHIN ANY BUILDING. | | | | | | 3. 2020 FRC P2801.1 REQUIRED - IT DOES NOT APPEAR THAT | | | HOT WATER WAS SUPPLIED TO THE WASHING MACHINE AND IS | | | REQUIRED TO BE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] |
|