| 2022-10-17 08:59:21 | 1ST GAS REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.2.1 - IT IS NOT CLEAR WHERE THE |
| | DRYER IS. THERE IS A GAS DETAIL THAT SHOWS 1" PE GOING |
| | TO A DRYER BUT THE DRYER IS NOT ON THE FLOOR PLAN. |
| | CLARIFY. |
| | |
| | 2. 2020 FRC G2439.5 (614.6) WHEN DETAILING THE DRYER, |
| | PLEASE SHOW MAKEUP AIR FOR DRYER. PLEASE SHOW THE |
| | CALCULATION FOR THE REQUIREMENT OR EXCEPTION TO THE |
| | NEED FOR MAKE-UP AIR FOR THE DRYER. |
| | |
| | 3. 2020 FRC G2415.17.1 (404.17.1) WHEN DETAILING THE |
| | GAS LINE TO THE DRYER, PLEASE NOT THAT PLASTIC GAS LINE |
| | SHALL BE INSTALLED OUTDOORS UNDERGROUND ONLY. IT SHALL |
| | NOT BE USED WITHIN OR UNDER ANY BUILDING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |