| Plan Review Notes For Permit 22091175 |
| Permit Number |
22091175 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-09-30 11:09:49 | FIRE PROVISO COMMENTS: | | | | | | (1) ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE | | | ALARM) SHALL REMAIN OPERATIONAL DURING ALL PHASES OF | | | DEMOLITION AND CONSTRUCTION. | | | | | | (2) ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE | | | SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS | | | HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A | | | FIRE WATCH. | | | | | | (3) ANY WORK ON ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER | | | AND/OR FIRE ALARM) SHALL BE DONE UNDER SEPARATE PERMITS | | | AND SHOP DRAWINGS BY PROPERLY LICENSED AND CERTIFIED | | | CONTRACTORS. | | | | | | (4) ANY INSTALLATION OF AN ACCESS CONTROL SYSTEM SHALL | | | BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY | | | PROPERLY CERTIFIED CONTRACTORS. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|