Plan Review Notes
Plan Review Notes For Permit 22091175
Permit Number 22091175
Review Stop E
Sequence Number 1
Notes
Date Text
2022-10-17 16:07:54ELECTRIC REVIEW FAILED
  
 1) PLEASE DETAIL THE NEW LOCATION THE 30KVA TRANSFORMER
 FEEDING PANEL "A" INSIDE SUITE 900. PLEASE INDICATE ON
 THE FLOOR PLAN WHERE IT HAS BEEN RELOCATED FROM. FBC
 107.2
 2) PLEASE INDICATE PRIMARY AND SECONDARY CONDUCTOR
 SIZES FOR 3O KVA TRANSFORMER AND SYSTEM BONDING JUMPER.
 NEC 215.5
 3) PLEASE INDICATE ON FLOOR PLAN AND RISER DIAGRAM THAT
 THE REQUIRED LABELS WILL BE IN PLACE DESIGNATING THE
 PRIMARY DISCONNECT LOCATION AND THAT IT IS LOCKABLE AS
 PER NEC 450.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  