| Plan Review Notes For Permit 22091175 |
| Permit Number |
22091175 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-17 16:07:54 | ELECTRIC REVIEW FAILED | | | | | | 1) PLEASE DETAIL THE NEW LOCATION THE 30KVA TRANSFORMER | | | FEEDING PANEL "A" INSIDE SUITE 900. PLEASE INDICATE ON | | | THE FLOOR PLAN WHERE IT HAS BEEN RELOCATED FROM. FBC | | | 107.2 | | | 2) PLEASE INDICATE PRIMARY AND SECONDARY CONDUCTOR | | | SIZES FOR 3O KVA TRANSFORMER AND SYSTEM BONDING JUMPER. | | | NEC 215.5 | | | 3) PLEASE INDICATE ON FLOOR PLAN AND RISER DIAGRAM THAT | | | THE REQUIRED LABELS WILL BE IN PLACE DESIGNATING THE | | | PRIMARY DISCONNECT LOCATION AND THAT IT IS LOCKABLE AS | | | PER NEC 450.14 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|