Plan Review Notes
Plan Review Notes For Permit 22091167
Permit Number 22091167
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-09-30 14:46:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE CONSTRUCTION OF A NEW
 BEDROOM IN AN AREA THAT HAS FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 THERE IS NO INDICATION OF FIRE SPRINKLER AND FIRE ALARM
 WORK.
  
 PER NFPA AN EVALUATION OF THE BOTH SYSTEMS FOR CODE
 COMPLIANT COVERAGE.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGMENT TO COMPLY.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  