Plan Review Notes
Plan Review Notes For Permit 22091167
Permit Number 22091167
Review Stop B
Sequence Number 1
Notes
Date Text
2022-10-25 09:07:01WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22091167
 ADD: 3960 N FLAGLER DR. #206
 CONT: PACIFIC PLUMBING SERVICE
 TEL: 305-962-2736
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 25TH/ 2022
 ACTION: DENIED
 3960 N FLAGLER DR
 BUILT IN 2007/ MID RISE CONDOMINIUM
 BOTH FIRE ALARM & FIRE SPRINKLERS
  
 1) THE PERMIT VALUE IS STATED AT $3,000.00 DOLLARS IN
 VALUE, VALUE SEEMS LOW.
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS. FIRE SPRINKLER PERMIT VALUE NOT TO BE
 INCLUDED UNDER THIS MASTER PERMIT.
  
 2) SHEET A-1 INDICATES A NEW BEDROOM, BUT THE PLANS
 FAIL TO ADDRESS WITH THE NEW WALLS AND A CONCRETE
 FLOOR/ CEILING ASSEMBLY ABOVE HOW WILL THE NEW FIRE
 SPRINKLER PIPES GOING TO BE RUN INTO THE NEW ROOM TO
 ACHIEVE COVERAGE OF ALL WALLS. 107.2.1 CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 3) THIS BUILDING WAS BUILT IN 2007 AND IS COVERED UNDER
 THE FAIR HOUSING ACT. . FAIR HOUSING ACT DESIGN AND
 CONSTRUCTION REQUIREMENTS. FOR PURPOSES OF THIS
 SECTION, A COVERED MULTIFAMILY DWELLING SHALL BE DEEMED
 TO BE DESIGNED AND CONSTRUCTED FOR FIRST OCCUPANCY ON
 OR BEFORE MARCH 13, 1991, IF THEY ARE OCCUPIED BY THAT
 DATE OR IF THE LAST BUILDING PERMIT OR RENEWAL THEREOF
 FOR THE COVERED MULTIFAMILY DWELLINGS IS ISSUED BY A
 STATE, COUNTY OR LOCAL GOVERNMENT ON OR BEFORE JANUARY
 13, 1990.
 THE FLOOR PLAN INDICATES DOOR NUMBER (1) TO BE
 32-INCH-WIDE DOOR. IN THE 2020 FBC-ACCESSIBILITY CODE
 BACK OF BOOK, FAIR HOUSING ACCESSIBILITY GUIDELINES /
 DESIGN GUIDELINES FOR ACCESSIBLE/ ADAPTABLE DWELLINGS.
 PAGE 8 SECTION 100.205??(2) (2) WITHIN DWELLING UNITS
 DOORS INTENDED FOR THE USER PASSAGE THROUGH THE UNIT
 WHICH HAVE A CLEAR OPENING OF AT LEAST 32 INCHES
 NOMINAL WIDTH WHEN THE DOOR IS OPEN 90 DEGREES,
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE DOOR
 STOP. SEE FIGURE (A) FOR HINGED DOORS. NOTE A
 34-INCH-WIDE DOOR WILL MEET THIS REQUIREMENT.
  
 4) THE PLANS ARE SILENT IF THERE IS TO BE A CHANGE IN
 FLOORING? 107.2.1 ADDITIONAL INFORMATION MAYBE
 REQUIRED.
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  