2023-02-28 13:26:16RESIDENTIAL (R3) THIRD BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22091140
 2912 S OLIVE AVE
  
 1- PLANS AND DOCUMENTS SUBMITTED ARE SIGNED AND SEALED
 BY PAUL H. ORR P.E. #64898. ACCORDING TO DEPARTMENT OF
 BUSINESS & PROFESSIONAL REGULATION (DBPR) THIS ENGINEER
 IS DECEASED. PLANS AND DOCUMENTS CANNOT BE ACCEPTED.
 SEC. 471.025 F.S.
  
 ORIGINAL COMMENT:
 2-FLOOR PLAN SHOWS REPLACEMENT OF EXTERIOR DOORS FOR
 MASTER BEDROOM AND FAMILY ROOM. ACCORDING TO CITY
 RECORDS THESE TWO ROOMS ARE GARAGE AND PORCH
 RESPECTIVELY. THERE ARE NO PERMITS IN THE CITY RECORDS
 FOR CONVERSION OF GARAGE AND PORCH. IT LOOKS LIKE THESE
 ENCLOSURES WERE DONE WITHOUT RESPECTIVE PERMITS. NEED
 TO PROVIDE COMPLETE SET OF PLANS SHOWING PROPOSED
 CONVERSION. SEC. 105.1 CITY AMENDMENTS.
  
 PREVIOUS COMMENT:
 4- BUILDING THERMAL ENVELOPE. ENGINEER OF RECORD NEEDS
 TO DEPICT THE BUILDING THERMAL ENVELOPE. NEED TO
 SPECIFY INSULATION MATERIALS AND THEIR R-VALUES.(ROOF,
 WALLS, RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY
 SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 5- ENGINEER OF RECORD TO SPECIFY ALL THE WIND DESIGN
 CRITERIA AS REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
 SPECIFY THE ULTIMATE AND NOMINAL WIND LOAD, BUILDING
 EXPOSURE, BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE
 COMPONENTS AND CLADDING DESIGN PRESSURES. (DOORS,
 WINDOWS).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 6- ENGINEER OF RECORD TO CLARIFY WHAT IS "TYPE 1B"
 SPECIFIED ON SHEET A-1 UNDER "STATS". IF ENGINEER IS
 SPECIFYING THE TYPE OF CONSTRUCTION, THEN IT IS
 INCORRECT. ENGINEER TO SEE SEC. 602 FBC-BUILDING AND
 REVISE CONSTRUCTION TYPE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 7- A LANDING IS REQUIRED ON THE OUTSIDE OF THE FAMILY
 ROOM FRENCH DOORS. SEC. R311.3 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 8-DOOR PRODUCT APPROVAL SUBMITTED IS INCOMPLETE. NEED
 TO PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL, INCLUDING
 THE FLORIDA PRODUCT APPROVAL COVER PAGE THAT
 CORRESPONDS TO THE DRAWINGS SUBMITTED. FAC 61G20.3.001
 NOTE: THE FLORIDA PRODUCT APPROVAL IS REQUIRED BECAUSE
 IT SHOWS IF PRODUCT IS APPROVED AND CURRENT CODE IN
 EFFECT. CHAPTER 553 F.S.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 9-PROVIDE PRODUCT APPROVAL FOR ENTRY INSWING SINGLE
 ENTRY DOOR AS SHOWN ON FLOOR PLAN.
 FAC 61G20.3.001.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 PREVIOUS COMMENT:
 10-ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PREVIOUS COMMENT:
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
 NOTE: THE VALUE IS TO INCLUDE ALL WORK TO RENOVATE THE
 RESIDENCE WITH NEW MASTER BEDROOM, FLORIDA ROOM AND
 REST OF THE HOUSE AS SHOWN ON PLANS.
  
 11- ORIGINAL PERMIT APPLICATION WAS FOR REPLACEMENT OF
 3 EXISTING DOORS. ACCORDING TO ITEM #2 ABOVE, THE SCOPE
 OF WORK NEEDS TO BE DONE FOR GARAGE AND PORCH
 CONVERSION TO HABITABLE SPACES. THE PERMIT APPLICATION
 NEEDS TO BE REVISED TO SHOW THE CONVERSION OF THE
 GARAGE AND PORCH TO LIVABLE SPACE. VALUE NEEDS TO BE
 INCREASED ALSO. SEE VALUATION COMMENT ABOVE. SEC.
 107.2.1 CITY AMENDMENTS.
 NOTE: THIS WILL ALSO HELP TO CLARIFY TO THE OTHER PLANS
 REVIEWERS THE ACTUAL SCOPE OF WORK AND TO AVOID MORE
 CONFLICTS.
  
 13- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR WALL
 FLASHING AT ALL EXTERIOR OPENINGS. SEC. R703.4
 FBC-RESIDENTIAL.
  
 14- MASTER BATHROOM AND WATER CLOSET COMPARTMENT NEEDS
 VENTILATION AS REQUIRED BY SEC. R303.3 FBC-RESIDENTIAL.
 ENGINEER TO SPECIFY HOW PROVIDING THE REQUIRED
 VENTILATION.
  
 15- REVISED DRAWING A-1 SHOWS NEW SWALES AND FRENCH
 DRAIN DETAIL. PROVIDE SITE PLAN SHOWING THE ACTUAL
 LOCATION OF THESE WORK. SEC. 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER