Plan Review Notes
Plan Review Notes For Permit 22091119
Permit Number 22091119
Review Stop P
Sequence Number 1
Notes
Date Text
2022-10-05 16:04:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22091119 1401 NORTHPOINT PKWY
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1. ID.0.2.1: THE SIDE WALL GRAB BAR SHALL EXTEND A
 MINIMUM OF 54 INCHES MINIMUM FROM THE REAR WALL PER FBC
 ACC 604.5.1
  
 2. ID.0.2.1: PER FBC ACC 609.4, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM
 AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP (NOT THE CENTER) OF THE GRIPPING SURFACE
  
 3. SHOW CLEAR FLOOR SPACES AND FOR ALL ACCESSIBLE
 PLUMBING FIXTURES ON PLAN INCLUDING SINKS (FBC ACC
 606.2, 305.3), LAVATORIES (FBC ACC 606.2, 305.3), WATER
 CLOSETS (FBC ACC 604.3.1, 604.8.1.1), URINALS (FBC ACC
 605.3, 305.3) AND DRINKING FOUNTAINS (FBC ACC 602.2,
 305.3).
  
 4. SHOW TURNING SPACE FOR ACCESSIBLE WATER CLOSETS (FBC
 ACC 304.3.1 OR 304.3.2)
  
 5. PER WPB FBC 107.2.1, PROVIDE PLAN AND ELEVATION VIEW
 OF DRINKING FOUNTAIN SHOWING COMPLIANCE WITH FBC ACC
 602.1, 602.2, 602.3, 602.4, 602.5, 602.7
  
 6. P-0.1/PLUMBING FIXTURE SCHEDULE CALL FOR FLOOR
 MOUNTED WATER CLOSETS. ID.7 ELEVATIONS INDICATE WALL
 HUNG WATER CLOSETS. PER WPB FBC 107.2.1, PLEASE CLARIFY
 AND RECONCILE. IF WALL HUNG, PROVIDE A WALL SUPPORT
 SYSTEM WITH DRAINAGE FITTING FOR THE FIXTURE.
  
 7. PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3(13),
 PROVIDE SIZED SANITARY RISER DIAGRAMS. SHOW ALL TRAPS,
 VENTS, TRAP PRIMER CONNECTIONS; SHOW AND TAG ALL
 FIXTURE/DRAIN CONNECTIONS TO CORRESPOND WITH PLUMBING
 FIXTURE SCHEDULE.
  
 8. PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3(13),
 PROVIDE SIZED WATER RISER DIAGRAMS. SHOW ALL APPLICABLE
 VALVES, WATER HAMMER ARRESTORS, TRAP PRIMERS, PUMPS AND
 OTHER APPLICABLE APPURTENANCES; SHOW AND TAG ALL
 FIXTURE/EQUIPMENT CONNECTIONS TO CORRESPOND WITH
 PLUMBING FIXTURE AND EQUIPMENT SCHEDULES.
  
 9. PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3(3),
 PROVIDE CALCULATIONS FOR SIZING OF WATER DISTRIBUTION.
 FBC PL 604.1, 604.3
  
 10. PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3(4),
 PROVIDE CALCULATIONS FOR SIZING OF SANITARY PIPING. FBC
 PL 709.1
  
 11. P-0.1/DETAIL 1: PER FBC PL 607.1.1, A THERMOSTAT
 CONTROL FOR A WATER HEATER SHALL NOT SERVE AS THE
 TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF
 COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR
 MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY
 TEMPERATURE AT FIXTURES. PROVIDE A THERMOSTATIC MIXING
 DEVICE WHICH CAN BE PUT AT EACH FIXTURE OR AT THE
 SOURCE OF HOT WATER (WATER HEATER). PLEASE NOTE, THIS
 PROVISION SHALL NOT SUPERSEDE THE REQUIREMENT FOR ASSE
 1070 COMPLIANT DEVICES FOR TEMPERED WATER TO PUBLIC
 LAVATORIES AS REQUIRED BY FBC PL 419.4.
  
 12. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 13. PER WPB FBC 107.2.1, IF APPLICABLE, PROVIDE A SLAB
 REPAIR DETAIL ON THE PLANS. SHOW THE WIDTH OF THE
 REPAIR, THE MINIMUM THICKNESS AND PSI OF THE CONCRETE
 TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON CENTER),
 MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE MATERIAL FOR
 DOWELS. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT
 OF THE SOIL AS WELL AS THE REQUIRED VAPOR BARRIER OVER
 WELL COMPACTED SOIL. A COPY OF THE TERMITE CERTIFICATE
 SHALL BE ONSITE FOR FINAL INSPECTION.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved