| Plan Review Notes For Permit 22091117 |
| Permit Number |
22091117 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-31 11:46:22 | 1ST REVIEW FMC | | | PERMIT: 22091117 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE MASTER PERMIT 21050305 DOES NOT SHOW A WALK-IN | | | COOLER ON EITHER THE LIFE SAFETY DRAWING OR THE | | | MECHANICAL DRAWINGS FOR THIS PROJECT. PROVIDE UPDATED | | | DRAWINGS FOR THE MASTER SHOWING THE LOCATION OF THE | | | WALK-IN COOLER AND THE CONDENSER FOR THIS COOLER. | | | PROVIDE A MECHANICAL DRAWING FOR THIS WALK-IN COOLER | | | SUBMITTAL THAT IDENTIFIES THE LOCATIONS OF THE WALK-IN | | | COOLER AND CONDENSING UNIT. FBC 107.3.5 | | | | | | 2) THE DESIGNER OF THE REFRIGERATION SYSTEM MUST | | | DIGITALLY SIGN THE DOCUMENTS. ALSO PROVIDE THE CORRECT | | | ADDRESS ON THE DOCUMENTS FOR THIS INSTALLATION. FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|