2022-10-31 11:46:221ST REVIEW FMC
 PERMIT: 22091117
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MASTER PERMIT 21050305 DOES NOT SHOW A WALK-IN
 COOLER ON EITHER THE LIFE SAFETY DRAWING OR THE
 MECHANICAL DRAWINGS FOR THIS PROJECT. PROVIDE UPDATED
 DRAWINGS FOR THE MASTER SHOWING THE LOCATION OF THE
 WALK-IN COOLER AND THE CONDENSER FOR THIS COOLER.
 PROVIDE A MECHANICAL DRAWING FOR THIS WALK-IN COOLER
 SUBMITTAL THAT IDENTIFIES THE LOCATIONS OF THE WALK-IN
 COOLER AND CONDENSING UNIT. FBC 107.3.5
  
 2) THE DESIGNER OF THE REFRIGERATION SYSTEM MUST
 DIGITALLY SIGN THE DOCUMENTS. ALSO PROVIDE THE CORRECT
 ADDRESS ON THE DOCUMENTS FOR THIS INSTALLATION. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  