Notes
Date Text
2023-04-26 07:29:022ND GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FRC G2415.11 - "SCHEDULE 40 METALLIC PIPE" IS
 NOT ALLOWED TO BE INSTALLED UNDERGROUND.
  
 2. 2020 FRC G2415.8 - THE PIPING GOING TO THE RANGE
 APPEARS TO BE IN A SOLID FLOOR. SHOW COMPLIANCE WITH
 THIS SECTION OR SHOW IT GOING OVERHEAD.
  
 3. 2020 FRC G2415.8 - THE PIPING GOING TO THE DRYER
 APPEARS TO BE IN A SOLID FLOOR. SHOW COMPLIANCE WITH
 THIS SECTION OR SHOW IT GOING OVERHEAD.
  
 4. 2020 FRC G2407.1 - PLEASE SHOW THE REQUIRED
 COMBUSTION AIR CALCULATIONS FOR THE DRYER. IF THE SPACE
 FOR THE DRYER DOES NOT HAVE ENOUGH FOR THE APPLIANCE,
 DETAILS MUST BE SHOWN ON THE PLANS FOR
 COMBUSTION/MAKEUP AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  