| 2022-12-14 09:41:41 | ELECTRIC REVIEW FAILED |
| | 1) PLAN INDICATES TWO LOCATIONS FOR ELECTRIC PANEL, ONE |
| | IN LAUNDRY ROOM AND ONE IN THE GARAGE. PLEASE CLARIFY |
| | WHICH LOCATION IS TO BE USED. IN ADDITION, ELECTRIC |
| | PANEL IN LAUNDRY ROOM DOES NOT APPEAR TO COMPLY WITH |
| | NEC 110.26 FOR WORKING CLEARANCE. FBC 107.2 |
| | 2) PLEASE DETAIL, ON THE ELECTRICAL PLAN, THE REQUIRED |
| | SMOKE/CARBON ALARMS AS PER FBC 314. |
| | 3) PLEASE DETAIL THE REQUIRED OUTSIDE RECEPTACLES AT |
| | THE FRONT OF THE HOUSE AS REQUIRED PER NEC 210.52(E)(1) |
| | 4) PLEASE DETAIL A NOTE STATING POOL AND GENERATOR |
| | WIRING REQUIRE A SEPARATE PERMIT |
| | 5) PLEASE DETAIL ON THE ELECTRIC PLAN THE WATER HEATER |
| | LOCATION AND TYPE, GAS OR ELECTRIC. FBC 107.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |