| 2022-12-12 13:53:22 | NEW SFR |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) PRODUCT APPROVALS LISTED ON |
| | THE DRAWINGS. |
| | |
| | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE ROOFING TILE - PLEASE CIRCLE |
| | THE TILE ATTACHMENT TYPE IN THE PRODUCT APPROVAL - IF |
| | USING ADHESIVE TO ATTACH THE TILE PROVIDE THE PRODUCT |
| | APPROVAL FOR THE ADHESIVE. |
| | |
| | 3) PLEASE SHOW THE ATTIC ACCESS OPENING SIZE ( 22" X |
| | 30" ) - FBC R807.1 ATTIC ACCESS. |
| | BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION |
| | SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT |
| | HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR GREATER |
| | OVER AN AREA OF NOT LESS THAN 30 SQUARE FEET (2.8 M2). |
| | THE VERTICAL HEIGHT SHALL BE MEASURED FROM THE TOP OF |
| | THE CEILING FRAMING MEMBERS TO THE UNDERSIDE OF THE |
| | ROOF FRAMING MEMBERS. THE ROUGH-FRAMED OPENING SHALL BE |
| | NOT LESS THAN 22 INCHES BY 30 INCHES (559 MM BY 762 MM) |
| | AND SHALL BE LOCATED IN A HALLWAY OR OTHER LOCATION |
| | WITH READY ACCESS. |
| | |
| | 4) PLEASE SHOW THE GARAGE FLOOR TO SLOPE - FBC R309.1 |
| | THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR |
| | OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE |
| | MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN |
| | VEHICLE ENTRY DOORWAY. |
| | |
| | 5) THE WIND DESIGN IS SHOWN USING EXPOSURE "C". WITH |
| | THE LOCATION OF THE PROPERTY LOCATED ON THE LARGE LAKE |
| | EXPOSURE "D" SHOULD BE USED FOR THE WIND DESIGN. FBC |
| | R301.2.1.4.3 EXPOSURE D SHALL APPLY WHERE THE GROUND |
| | SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, |
| | PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT |
| | LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE |
| | BUILDING, WHICHEVER IS GREATER. |
| | |
| | 6) THE SIGNED AND SEALED SOIL REPORT PROVIDED DOES NOT |
| | SHOW AS DIGITALLY SIGNED IN ADOBE READER. SIGNED AND |
| | SEALED DRAWINGS IN PROJECTDOX NEED TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| | SPECIFIC TYPE OF E-SIGNATURE). |
| | |