2022-10-17 11:01:26ELECTRIC REVIEW FAILED
  
 1) PLEASE DETAIL HOW 200 AMP MAIN BREAKER FEEDING A 160
 AMP RATED ENPHASE CONTROLLER.COMPLIES WITH NEC 110.9
 FOR MINIMUM RATING.
 2) PLANS INDICATE MAIN SERVICE LOCATED AT AUXILIARY
 STRUCTURE. ONE LINE DIAGRAM DOES NOT DETAIL THE
 REQUIRED GROUNDING ELECTRODE SYSTEM A MAIN HOUSE AS
 REQUIRED PER NEC 250.32
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  