| 2023-01-03 09:06:53 | 2ND REVIEW FMC |
| | PERMIT: 22091089 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-130: OUTDOOR AIR CALCULATIONS FOR AHU-1; IT |
| | APPEARS THAT THE LOBBIES/PREFUNCTION CALCULATIONS IS |
| | USING THE WRONG OCCUPANCY DENSITY. THE OCCUPANCY |
| | DENSITY FOR LOBBIES/PREFUNCTION SHOULD BE 30 AND NOT |
| | 10. THIS HAS MADE THE OUTDOOR AIR CALCULATION TOO LOW |
| | FOR THE SPACE. PLEASE CHECK THE NUMBERS AND MAKE THE |
| | REQUIRED CORRECTIONS. FMC 403.3.1.1 |
| | |
| | 2) PLEASE PROVIDE THE AHU SYSTEM VENTILATION RATE |
| | COMPLETE CALCULATION FOR EACH AHU. FMC 403.3.1.1 |
| | |
| | 3) PROVIDE THE REQUIRED EXHAUST FOR THE COPY/PRINT |
| | AREA. FMC TABLE 403.3.1.1 |
| | |
| | 4) SHEET M-510: PLEASE SHOW HOW OUTDOOR AIR WILL BE |
| | INTRODUCED FOR THE 2ND FLOOR AHU-2. FBC 107.3.5 |
| | |
| | 5) PLEASE REFERENCE THE SHEET AND NOTE THAT STATES THE |
| | BATHROOM EXHAUST FANS ARE CONTINUOUSLY OPERATED, SHEET |
| | M-120 DOES NOT MENTION THE FANS ARE CONTINUOUSLY |
| | OPERATED. CONTROL INTERLOCKS DOES LIST SCHEDULE. FMC |
| | TABLE 403.3.1.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |