| 2022-11-07 13:06:19 | 1ST REVIEW FMC |
| | PERMIT: 22091089 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON |
| | THE OCCUPANCY CLASSIFICATIONS FOUND IN FMC TABLE |
| | 403.3.1.1. I CANNOT COMPARE THE SUBMITTED CALCULATIONS |
| | WITH TABLE 403.3.1.1. I CANNOT COMPARE THE CALCULATIONS |
| | UNTIL YOU PROVIDE ME WITH OCCUPANCIES IDENTIFIED FROM |
| | TABLE 403.3.1.1. FMC 403.3.1.1 |
| | |
| | 2) THE BATHROOM EXHAUST MUST MEET THE MINIMUM CFM???S |
| | BASED ON FMC TABLE 403.3.1.1. PLEASE SHOW THAT THE |
| | CFM???S WILL MEET THE 70 CFM???S PER WATER CLOSET OR |
| | URINAL. EXAMPLE: EF2-2 SHOULD HAVE A MINIMUM OF 420 |
| | CFM???S OF EXHAUST. 6 X 70 = 420. EF-1-5 SHOULD HAVE A |
| | MINIMUM OF 490 CFM???S. |
| | |
| | 3) SHEET M-300: NEW WORK NOTE 11 IS REFERENCING A |
| | EF1-6, THE IS NO EF-1-6 IN THE FAN SCHEDULE ON SHEET |
| | M-120. PLEASE CORRECT NEW WORK KEYNOTE 11. FBC 107.3.5 |
| | |
| | 4) REVISE THE MECHANICAL DRAWINGS TO SHOW THE DUCT |
| | DETECTORS IN THE SUPPLY SIDE OF THE DUCTWORK. FMC 606.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |