| 2022-10-31 13:45:48 | NEW 2 STORY CHURCH SUNDAY SCHOOL AND OFFICE |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS, |
| | LOUVERS, ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED |
| | TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING |
| | DESIGNER OF RECORD FBC WPB 107.3.4 |
| | |
| | 2) DRAWINGS SHOW BUILDING CONSTRUCTION TYPE AS II B - |
| | WOOD (TRUSSES, ROOF SHEATHING ETC.) USED IN |
| | CONSTRUCTION TYPE II BUILDINGS SHOULD BE FIRE RETARDANT |
| | PER FBC 603.1 |
| | |
| | 3) PLEASE PROVIDE A SITE PLAN - SHOWING THE FOLLOWING |
| | INFORMATION FBC WPB107.2.5 SITE PLAN. THE CONSTRUCTION |
| | DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT |
| | SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE |
| | THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| | WATER RETAINING SWALES) |
| | |
| | 4) PLEASE PROVIDE A SURVEY. |
| | |
| | 5) THE REAR RESTROOM WALLS ARE TILED - THE RESTROOM |
| | WALL FINISH ON THE WALL BESIDE THE TOILETS WILL ALSO |
| | NEED TO COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 6) PLEASE SHOW THE WALL FINISH SURROUNDING THE MOP |
| | SINK/SERVICE SINK TO COMPLY WITH FBC 1210.2.2 WALLS AND |
| | PARTITIONS. |
| | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| | CONSIDERED A HARD SURFACE) |
| | |
| | 7) A SEPARATE PERMIT IS REQUIRED FOR THE DUMPSTER |
| | ENCLOSURE AND THE CHILLER. |
| | |
| | 8) ITEMS SUCH AS BUT NOT LIMITED TO ROOFING SYSTEMS, |
| | WINDOW AND DOOR PRODUCT APPROVALS ETC. - MAY BE |
| | DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON |
| | THE CONSTRUCTION DOCUMENTS - 107.3.4.1 |
| | |
| | 9) THE SOIL REPORT PROVIDED NEEDS TO BE |
| | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| | PROJECTDOX (ELECTRONIC PLAN REVIEW). |