Plan Review Notes
Plan Review Notes For Permit 22091037
Permit Number 22091037
Review Stop M
Sequence Number 3
Notes
Date Text
2023-02-17 06:48:39APPROVED WITH PRIVISOS:
  
 THE CONTRACTOR WILL NEED TO PROVIDE GUARDS AT ALL
 EQUIPMENT ON THE ROOF THAT IS WITHIN THE ROOFS EDGE.
 FMC 304.11
  
 KEYNOTES 7 AND 8 WILL NOW REQUIRE A SEPARATE PERMIT AND
 REVIEW OF THE SOURCE CAPTURE CONTAINMENT SYSTEM. THIS
 SYSTEM SHALL BE ABLE TO SUPPORT EVERY BAY IN THIS
 FACILITY. FMC 502.14