Plan Review Notes
Plan Review Notes For Permit 22091037
Permit Number 22091037
Review Stop P
Sequence Number 2
Notes
Date Text
2022-12-28 06:48:542ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. THIS COMMNET NOT SATISFIED - THE 1070 DEVICE ON THE
 PUBLIC LAV DOES NOT COMPLY THIS COMMENT - THERE NEEDS
 TO BE A 1017 MIXING DEVICE ON THE WATER HEATER.
  
 2020 FPC 607.1.1 - THE THERMOSTAT ON THE WATER CANNOT
 SERVE AS THE LIMITING MEANS FOR HOT OR TEMPERED WATER.
 A MIXING DEVICE IS REQUIRED FOR THIS SECTION AND IS IN
 ADDITION TO THE LIMITING DEVICE REQUIRED FOR TEMPERED
 PUBLIC HANDWASHING. THE DEVICE MUST COMPLY WITH ASSE
 1017 AND MUST BE INSTALLED AT THE HOT WATER SOURCE PER
 2020 FPC 613.1. PLEASE MAKE THE CHANGES ON THE WATER
 HEATER DETAIL ON PAGE P0.1 AND THE ISOMETRIC ON PAGE
 P5.1.
  
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1