| 2023-01-11 06:14:49 | 2ND REVIEW FMC |
| | PERMIT: 22091037 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE REVISED ENERGY CALCULATIONS WERE NOT IN THIS 2ND |
| | SUBMITTAL. PLEASE ADDRESS THE FIRST CYCLE REVIEW |
| | COMMENT BELOW: |
| | 1) THE ENERGY CALCULATIONS FAIL TO MENTION ANY DOORS IN |
| | THE CALCULATIONS. ALL AREAS THAT ARE TO BE CONDITIONED |
| | MUST MEET THE FEC. PLEASE INCLUDE ALL DOORS IN THE |
| | CALCULATIONS. FEC C402 |
| | |
| | 2) THE REVISED HEAT LOAD CALCULATIONS WERE NOT IN THIS |
| | 2ND SUBMITTAL. PLEASE ADDRESS THE FIRST CYCLE COMMENT |
| | BELOW: |
| | |
| | 2) THE MECHANICAL EQUIPMENT CALCULATIONS ARE ONE PAGE |
| | AND ONLY FOR 593 SQ. FT. THE ENERGY CALCULATIONS |
| | INDICATE THAT 5739 SQ. FT. WILL BE CONDITIONED. PROVIDE |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR ALL AREAS |
| | THAT ARE TO BE CONDITIONED. FEC C403.2.1 |
| | |
| | 3) PLEASE UNDERSTAND THAT THE SOURCE CAPTURE |
| | CONTAINMENT SYSTEM DESIGN STILL NEEDS TO BE ADDRESSED, |
| | SEE BELOW: |
| | SOURCE CAPTURE SYSTEM. A MECHANICAL EXHAUST SYSTEM |
| | DESIGNED AND CONSTRUCTED TO CAPTURE AIR CONTAMINANTS AT |
| | THEIR SOURCE AND TO EXHAUST SUCH CONTAMINANTS TO THE |
| | OUTDOOR ATMOSPHERE. A HOSE THROUGH A HOLE IN A GARAGE |
| | IS NOT CONSIDERED A SYSTEM. |
| | |
| | 502.14 MOTOR VEHICLE OPERATION. IN AREAS WHERE MOTOR |
| | VEHICLES OPERATE, MECHANICAL VENTILATION SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 403. ADDITIONALLY, AREAS IN |
| | WHICH STATIONARY MOTOR VEHICLES ARE OPERATED SHALL BE |
| | PROVIDED WITH A SOURCE CAPTURE SYSTEM THAT CONNECTS |
| | DIRECTLY TO THE MOTOR VEHICLE EXHAUST SYSTEMS. |
| | |
| | SUCH SYSTEM SHALL BE ENGINEERED BY A REGISTERED DESIGN |
| | PROFESSIONAL OR SHALL BE FACTORY-BUILT EQUIPMENT |
| | DESIGNED AND SIZED FOR THE PURPOSE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |