2023-01-11 06:14:492ND REVIEW FMC
 PERMIT: 22091037
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED ENERGY CALCULATIONS WERE NOT IN THIS 2ND
 SUBMITTAL. PLEASE ADDRESS THE FIRST CYCLE REVIEW
 COMMENT BELOW:
 1) THE ENERGY CALCULATIONS FAIL TO MENTION ANY DOORS IN
 THE CALCULATIONS. ALL AREAS THAT ARE TO BE CONDITIONED
 MUST MEET THE FEC. PLEASE INCLUDE ALL DOORS IN THE
 CALCULATIONS. FEC C402
  
 2) THE REVISED HEAT LOAD CALCULATIONS WERE NOT IN THIS
 2ND SUBMITTAL. PLEASE ADDRESS THE FIRST CYCLE COMMENT
 BELOW:
  
 2) THE MECHANICAL EQUIPMENT CALCULATIONS ARE ONE PAGE
 AND ONLY FOR 593 SQ. FT. THE ENERGY CALCULATIONS
 INDICATE THAT 5739 SQ. FT. WILL BE CONDITIONED. PROVIDE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR ALL AREAS
 THAT ARE TO BE CONDITIONED. FEC C403.2.1
  
 3) PLEASE UNDERSTAND THAT THE SOURCE CAPTURE
 CONTAINMENT SYSTEM DESIGN STILL NEEDS TO BE ADDRESSED,
 SEE BELOW:
 SOURCE CAPTURE SYSTEM. A MECHANICAL EXHAUST SYSTEM
 DESIGNED AND CONSTRUCTED TO CAPTURE AIR CONTAMINANTS AT
 THEIR SOURCE AND TO EXHAUST SUCH CONTAMINANTS TO THE
 OUTDOOR ATMOSPHERE. A HOSE THROUGH A HOLE IN A GARAGE
 IS NOT CONSIDERED A SYSTEM.
  
 502.14 MOTOR VEHICLE OPERATION. IN AREAS WHERE MOTOR
 VEHICLES OPERATE, MECHANICAL VENTILATION SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 403. ADDITIONALLY, AREAS IN
 WHICH STATIONARY MOTOR VEHICLES ARE OPERATED SHALL BE
 PROVIDED WITH A SOURCE CAPTURE SYSTEM THAT CONNECTS
 DIRECTLY TO THE MOTOR VEHICLE EXHAUST SYSTEMS.
  
 SUCH SYSTEM SHALL BE ENGINEERED BY A REGISTERED DESIGN
 PROFESSIONAL OR SHALL BE FACTORY-BUILT EQUIPMENT
 DESIGNED AND SIZED FOR THE PURPOSE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  