Plan Review Notes
Plan Review Notes For Permit 22091037
Permit Number 22091037
Review Stop P
Sequence Number 1
Notes
Date Text
2022-10-29 09:18:261ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 607.1.1 - THE THERMOSTAT ON THE WATER
 CANNOT SERVE AS THE LIMITING MEANS FOR HOT OR TEMPERED
 WATER. A MIXING DEVICE IS REQUIRED FOR THIS SECTION AND
 IS IN ADDITION TO THE LIMITING DEVICE REQUIRED FOR
 TEMPERED PUBLIC HANDWASHING. THE DEVICE MUST COMPLY
 WITH ASSE 1017 AND MUST BE INSTALLED AT THE HOT WATER
 SOURCE PER 2020 FPC 613.1. PLEASE MAKE THE CHANGES ON
 THE WATER HEATER DETAIL ON PAGE P0.1 AND THE ISOMETRIC
 ON PAGE P5.1.
  
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  