| Plan Review Notes For Permit 22091037 |
| Permit Number |
22091037 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-29 09:18:26 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FPC 607.1.1 - THE THERMOSTAT ON THE WATER | | | CANNOT SERVE AS THE LIMITING MEANS FOR HOT OR TEMPERED | | | WATER. A MIXING DEVICE IS REQUIRED FOR THIS SECTION AND | | | IS IN ADDITION TO THE LIMITING DEVICE REQUIRED FOR | | | TEMPERED PUBLIC HANDWASHING. THE DEVICE MUST COMPLY | | | WITH ASSE 1017 AND MUST BE INSTALLED AT THE HOT WATER | | | SOURCE PER 2020 FPC 613.1. PLEASE MAKE THE CHANGES ON | | | THE WATER HEATER DETAIL ON PAGE P0.1 AND THE ISOMETRIC | | | ON PAGE P5.1. | | | | | | | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 |
|