| Date |
Text |
| 2022-11-07 14:06:38 | 1ST REVIEW FMC |
| | PERMIT: 22091037 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGY CALCULATIONS FAIL TO MENTION ANY DOORS IN |
| | THE CALCULATIONS. ALL AREAS THAT ARE TO BE CONDITIONED |
| | MUST MEET THE FEC. PLEASE INCLUDE ALL DOORS IN THE |
| | CALCULATIONS. FEC C402 |
| | |
| | 2) THE MECHANICAL EQUIPMENT CALCULATIONS ARE ONE PAGE |
| | AND ONLY FOR 593 SQ. FT. THE ENERGY CALCULATIONS |
| | INDICATE THAT 5739 SQ. FT. WILL BE CONDITIONED. PROVIDE |
| | MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR ALL AREAS |
| | THAT ARE TO BE CONDITIONED. FEC C403.2.1 |
| | |
| | 3) PLEASE SHOW THAT THE DESIGN OF THE MECHANICAL SYSTEM |
| | AND MORE PRECISELY THE EXHAUST FOR THE REPAIR GARAGE |
| | WILL COMPLY WITH FMC 401.3. THE DESIGN WITH THE SENSORS |
| | IS COVERED IN FMC 404 PARKING GARAGES. A PARKING GARAGE |
| | AND A REPAIR GARAGE ARE NOT THE SAME THING AND HAVE |
| | DIFFERENT REQUIREMENTS IN THE FMC. THE REPAIR GARAGE |
| | WILL NEED TO MEET THE EXHAUST REQUIREMENTS OF TABLE |
| | 403.3.1.1. |
| | |
| | 401.3 WHEN REQUIRED. VENTILATION SHALL BE PROVIDED |
| | DURING THE PERIODS THAT THE ROOM OR SPACE IS OCCUPIED. |
| | |
| | 4) PLEASE PROVIDE THE SOURCE CAPTURE SYSTEM FOR THE |
| | REPAIR GARAGE. FMC 502.14 |
| | |
| | 502.14 MOTOR VEHICLE OPERATION. IN AREAS WHERE MOTOR |
| | VEHICLES OPERATE, MECHANICAL VENTILATION SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 403. ADDITIONALLY, AREAS IN |
| | WHICH STATIONARY MOTOR VEHICLES ARE OPERATED SHALL BE |
| | PROVIDED WITH A SOURCE CAPTURE SYSTEM THAT CONNECTS |
| | DIRECTLY TO THE MOTOR VEHICLE EXHAUST SYSTEMS. SUCH |
| | SYSTEM SHALL BE ENGINEERED BY A REGISTERED DESIGN |
| | PROFESSIONAL OR SHALL BE FACTORY-BUILT EQUIPMENT |
| | DESIGNED AND SIZED FOR THE PURPOSE. |
| | |
| | EXCEPTIONS: |
| | 1. THIS SECTION SHALL NOT APPLY WHERE THE MOTOR |
| | VEHICLES BEING OPERATED OR REPAIRED ARE ELECTRICALLY |
| | POWERED. |
| | 2. THIS SECTION SHALL NOT APPLY TO ONE- AND TWO-FAMILY |
| | DWELLINGS. |
| | 3. THIS SECTION SHALL NOT APPLY TO MOTOR VEHICLE |
| | SERVICE AREAS WHERE ENGINES ARE OPERATED INSIDE THE |
| | BUILDING ONLY FOR THE DURATION NECESSARY TO MOVE THE |
| | MOTOR VEHICLES IN AND OUT OF THE BUILDING. |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |