Plan Review Notes
Plan Review Notes For Permit 22091037
Permit Number 22091037
Review Stop E
Sequence Number 1
Notes
Date Text
2022-11-07 16:20:20ELECTRIC REVIEW FAILED
  
 1) PLEASE DETAIL ALL RECEPTACLES IN GARAGE BAY 150
 VOLTS TO GROUND OR LESS, 50 AMPERES OR LESS, AS GFI
 PROTECTED AS PER NEC 511.12 NEC 210.8(B)(8), IE QUAD
 RECEPTACLES
 2) PLEASE DETAIL THE CLASSIFICATION OF THE OIL/
 EQUIPMENT ROOM, IF NO CLASSIFICATION IS REQUIRED PLEASE
 STATE NOT CLASSIFIED. FBC 107.2
 3) PLEASE CLARIFY AS TO WHY NO ELECTRIC METERING IS
 DETAILED ON RISER DIAGRAM. FBC 107.2
 4) PLEASE DETAIL A NOTE UNDERGROUND WIRING BELOW
 CLASSIFIED AREA IS TO COMPLY WITH NEC 511.8
 5) PLEASE PROVIDE A NOTE STATING FIRE ALARM, ACCESS
 CONTROL, SIGN OR OTHER LOW VOLTAGE WIRING REQUIRE
 SEPARATE PERMITS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  