Plan Review Notes
Plan Review Notes For Permit 22091037
Permit Number 22091037
Review Stop B
Sequence Number 1
Notes
Date Text
2022-10-31 16:58:26NEW AUTO SERVICE BAY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SOIL REPORT FBC 1803.1
  
 2) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON
 THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL - SEE GENERAL NOTE ON THE PRODUCT APPROVAL.
  
 3) PLEASE SHOW THE WALL FINISH SURROUNDING THE MOP SINK
 - FBC 1210.2.2WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 4) PLEASE SHOW THE DISTANCE FROM THE EXISTING BUILDING
 - FBC 602.1GENERAL.
 BUILDINGS AND STRUCTURES ERECTED OR TO BE ERECTED,
 ALTERED OR EXTENDED IN HEIGHT OR AREA SHALL BE
 CLASSIFIED IN ONE OF THE FIVE CONSTRUCTION TYPES
 DEFINED IN SECTIONS 602.2 THROUGH 602.5. THE BUILDING
 ELEMENTS SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS
 THAN THAT SPECIFIED IN TABLE 601 AND EXTERIOR WALLS
 SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS THAN THAT
 SPECIFIED IN TABLE 602.
  
 FBC 705.5 FIRE-RESISTANCE RATINGS.
 EXTERIOR WALLS SHALL BE FIRE-RESISTANCE RATED IN
 ACCORDANCE WITH TABLES 601 AND 602 AND THIS SECTION.
 THE REQUIRED FIRE-RESISTANCE RATING OF EXTERIOR WALLS
 WITH A FIRE SEPARATION DISTANCE OF GREATER THAN 10 FEET
 (3048 MM) SHALL BE RATED FOR EXPOSURE TO FIRE FROM THE
 INSIDE. THE REQUIRED FIRE-RESISTANCE RATING OF EXTERIOR
 WALLS WITH A FIRE SEPARATION DISTANCE OF LESS THAN OR
 EQUAL TO 10 FEET (3048 MM) SHALL BE RATED FOR EXPOSURE
 TO FIRE FROM BOTH SIDES.
  
 FBC 705.8 OPENINGS.
 OPENINGS IN EXTERIOR WALLS SHALL COMPLY WITH SECTIONS
 705.8.1 THROUGH 705.8.6.
  
 5) FIRE SPRINKLERS - FBC 903.2.9.1REPAIR GARAGES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED
 THROUGHOUT ALL BUILDINGS USED AS REPAIR GARAGES IN
 ACCORDANCE WITH SECTION 406, AS SHOWN: A GROUP S-1 FIRE
 AREA USED FOR THE REPAIR OF COMMERCIAL MOTOR VEHICLES
 WHERE THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464 M2).
  
 6) DRAWING A0.0 - BUILDING DATA - 1 STORY WITH PARTIAL
 UPPER LEVEL OFFICE AREA - DRAWINGS DO NOT SHOW AN UPPER
 LEVEL - PLEASE CLARIFY.
  
 7) PLEASE PROVIDE A SITE PLAN SHOWING THE FOLLOWING
 INFORMATION FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 8) PLEASE PROVIDE A SURVEY.
  
 9) ACCESSIBLE RESTROOM - PLEASE SHOW MAXIMUM GRAB BAR
 HEIGHTS TO THE TOP OF THE GRIPPING SURFACE - NOT THE
 CENTER OF THE BAR AS SHOWN ON THE DRAWING - FBC A 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 10) PLEASE SHOW THE DIMENSION OF THE TOILET PAPER
 HOLDER FROM THE FACE OF THE TOILET PER FBC A 604.7
 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  