2022-10-25 09:04:261ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22091033
 10/25/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P1.1: PLEASE SHOW THE CLEARANCE DISTANCE MEASUREMENT
 FOR THE GAS WATER HEATER TO THE WINDOW, AND OTHER
 OPENINGS INTO THE BUILDING SUCH AS, THE OVERHEAD
 VENTILATED SOFFIT- SECS. G2427.8 & G2448.1 FBC RES.
  
 2) P1.1 & P2.1: INDICATE HOW COMBUSTION AIR WILL BE
 PROVIDED TO THE RANGE AND PROVIDE CALCULATIONS- SECTION
 G2407.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  