Plan Review Notes
Plan Review Notes For Permit 22090996
Permit Number 22090996
Review Stop G
Sequence Number 1
Notes
Date Text
2022-10-13 06:51:311ST GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 ALTHOUGH THE GAS DRAWING WAS NOT SUBMITTED WITH THIS
 REVISION, IT WAS NOTICED THAT THERE IS A UNVENTED GAS
 FIREPLACE IN THE BEDROOM WHICH IS NOT ALLOWED PER 2020
 FRC G2406.2. SO A RE-REVIEW OF THE ORIGINAL PLANS HAVE
 FOUND THE FOLLOWING.
  
 1. 2020 FRC G2406.2 - AN UNVENTED FIREPLACE CANNOT BE
 IN A BEDROOM UNLESS IT FALLS UNDER ONE OF THE
 EXCEPTIONS OF THIS CODE SECTION. IN SAYING IT IS
 UNVENTED, IT DOES NOT FIT ONE OF THE EXCEPTIONS.
 HOWEVER, ON PAGE 13 AC-2 AC 2ND FLOOR PLAN OF THE
 MASTER SET, THERE'S A NOTE THAT STATES THIS IS AN
 "URBANA U50I-NG"?. IF THIS IS THE CASE, SUBMIT THE
 VENTING DETAILS ASSOCIATED WITH THIS FIREPLACE TO SHOW
 COMPLIANCE WITH THE CODE.
  
 2. 2020 FRC G2413.3 - I WAS UNABLE TO FIND THE PIPE
 SIZING CALCULATIONS ON THE ORIGINAL SET OF PLANS.
 PLEASE AMEND PAGE 35 P-8 PLUMBING SPECIFICATIONS AND
 SHOW THE PIPE SIZING CALCULATIONS. INCLUDE THE SIZING
 METHOD USED, PIPE SIZES, LONGEST RUN, PIPE PRESSURES,
 ETC.
  
 3. 2020 FRC G2415.11.1 - THERE IS A NOTE ON PAGE 35 P-8
 THAT SAYS "ALL GAS PIPING TO BE GALVANIZED OR STEEL -
 SCHD 40". HOWEVER, YOUR DETAILS APPEAR TO SHOW
 UNDERGROUND GAS PIPING. STEEL THREADED PIPE AND/OR
 GALVANIZED IS NOT ALLOWED UNDERGROUND UNLESS IT MEETS
 SEVERAL STANDARDS AND PROTECTION LEVELS IN ACCORDANCE
 WITH G2415.11.2, WHICH IS EXTREMELY UNUSUAL. PLEASE
 DETAIL THE PIPING DIAGRAM TO SHOW COMPLIANCE WITH
 UNDERGROUND PIPING.
  
 4. 2020 FRC G2439.5 - PLEASE INCLUDE WITH THE SET OF
 PLANS DETAILS SHOWING COMPLIANCE WITH, OR THE LACK OF
 NEED FOR MAKE UP AIR ASSOCIATED WITH THIS CODE SECTION
 FOR THE TWO DRYERS.
  
  
 PLEASE RESUBMIT WITH ALL GAS DRAWINGS AND DETAILS FOR
 REVIEW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  