Plan Review Notes For Permit 22090958
Permit Number 22090958
Review Stop P
Sequence Number 2
Notes
Date Text
2023-01-09 07:09:012ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. DONE
  
 2. NOT COMPLIED. THIS COMMENT ADDRESSES ALL WATER
 COMING FROM THE WATER HEATER. THERE SHOULD BE A MIXING
 DEVICE ADDED TO THE WATER HEATER. IT SHOULD BE SHOWN ON
 THE WATER HEATER DETAIL AND THE ISOMETRIC. THE DETAIL
 YOU HAVE FOR THE PUBLIC LAVS SHOULD SHOW COMPLIANCE
 WITH 1070 ONLY, NOT 1017, 1070 AND 1069.
 PAGE P-08 - 2020 FPC 607.1.1 - PLEASE SHOW COMPLIANCE
 WITH THE LIMITING FOR HOT WATER DELIVERY. THE
 THERMOSTAT ON THE WATER CANNOT SERVE AS THE LIMITING
 MEANS FOR HOT OR TEMPERED WATER. A MIXING DEVICE IS
 REQUIRED FOR THIS SECTION AND IS IN ADDITION TO THE
 LIMITING DEVICE REQUIRED FOR TEMPERED PUBLIC
 HANDWASHING. THE DEVICE MUST COMPLY WITH ASSE 1017 AND
 MUST BE INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC
 613.1.
  
 3. DONE
  
 4. DONE
  
 5. DONE
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved