| 2023-01-11 13:41:09 | 2ND REVIEW FMC |
| | PERMIT: 22090958 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-02: AHU-1 SERVES THE BAR AND DINING ROOM. |
| | BOTH WILL NEED OUTDOOR AIR. PLEASE SHOW THE OUTDOOR AIR |
| | DUCT AND TERMINATION LOCATION FOR AHU-1. FMC 403.3.1.1 |
| | |
| | 2) IT APPEARS THAT THE AHU-3 IS INSTALLED ABOVE THE |
| | CEILING AT THE BATHROOMS LOCATION. SHOW THE ACCESS FOR |
| | SERVICING FOR THIS UNIT AND ALL OF THE AHU???S. FMC |
| | 306.1 |
| | |
| | 3) PLEASE SHOW THE RETURN AIR PATH FROM THE DINING ROOM |
| | BACK TO AHU-3. FMC 601.6 |
| | |
| | 4) SHEET M-03: PROVIDE DETAILS ABOUT THE PROTECTION OF |
| | THE CONDENSING UNITS LOCATION IN THE PARKING GARAGE. |
| | FMC 303.4 |
| | |
| | 5) SHEET M-04: AIR BALANCE SCHEDULE HAS A NOTE AT THE |
| | TOP OF THE SCHEDULE THAT STATES - OUTDOOR DOOR WILL |
| | OPEN DURING BUSINESS OF OPERATION. WHY IS THIS NOTE |
| | HERE? WHAT ARE YOU TRYING TO ACHIEVE? FMC 508.1 |
| | |
| | 6) SHEET M-04: SHOW THE REQUIRED MAKE-UP AIR AND THAT |
| | IT MEETS THE TEMPERATURE LIMITATION OF FMC 508.1.1 |
| | |
| | 7) SHEET M-04: THE AIR BALANCE SCHEDULE LISTS KITCHEN |
| | MAKE-UP AIR AS 1,800. PLEASE SHOW HOW THIS MAKE-UP AIR |
| | IS BEING INTRODUCED TO THE HOODS. FMC 508.1 |
| | |
| | MECHANICAL MAKEUP AIR SYSTEMS SHALL BE AUTOMATICALLY |
| | CONTROLLED TO START AND OPERATES SIMULTANEOUSLY WITH |
| | THE EXHAUST SYSTEM. |
| | |
| | 8) PLEASE EXPLAIN THE 1 INCH INTERNAL INSULATION INSIDE |
| | THE OUTDOOR AIR DUCT FOR AHU-3. |
| | |
| | 9) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH USE OF |
| | SPACE IN THIS TENANT SPACE. INCLUDE THE BAR IN THE |
| | OUTDOOR AIR CALCULATIONS FMC 403.3.1.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |