| 2023-01-09 10:14:35 | THERE ARE NO INDICATIONS THAT FIRE COMMENTS WERE |
| | ADDRESSED/CORRECTED. |
| | |
| | THE PREVIOUS COMMENTS FROM FIRE ARE PROVIDED BELOW. |
| | |
| | PLEASE PROVIDE SPECFIC RESPONSES TO EACH COMMENT. |
| | |
| | ******************************************************* |
| | ********************************** |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 02 - THERE IS AN INDICATION OF AN EXIT FROM |
| | THE KITCHEN INTO A PARKING GARAGE; HOWEVER, THERE IS NO |
| | INDICATION FO THE TRAVEL DISTANCE NOR TRAVEL PATH FROM |
| | THE EXIT DOOR THROUGH THE PARKING GARAGE. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THETRAVEL PATH |
| | & TRAVEL DISTANCE PER NFPA 101, CH 12 & CH 7 MEANS OF |
| | EGRESS, TO A PUBLIC WAY. |
| | |
| | |
| | |
| | 2) SHEETS A 02 & A 03 - THERE ARE NO INDICATIONS OF 3 |
| | DOOR #'S ON THE FLOOR PLAN CORRESPONDING TO THE DOOR |
| | SCHEDULE. |
| | |
| | THOUGH THEY MAY BE EXISTING THEY NEED TO ID'D ON THE |
| | DOOR SCHEDULE SHOWING COMPLIANCE WITH THE REQUIRED EXIT |
| | LOCK/LATCH/HARDWARE PER NFPA 101, CH 12 & CH 7 MEANS OF |
| | EGRESS. |
| | |
| | PLEASE EPROVIDE THE REQUIRED DETAILS. |
| | |
| | |
| | |
| | 3) SHEET FS 0 & 1 - THE HOOD AND FIRE SUPPRESSION |
| | SYSTEMS SHALL BE SUBMITTED UNDER SEPARATE PEMITST AND |
| | SHOP DRAWINGS PER NFPA 96 & 17A |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT & COMPLIANCE. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |