| 2022-11-01 12:18:13 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE |
| | FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE |
| | WASTE. PLEASE SHOW THAT THE ICE BIN, HAND SINKS, ICE |
| | BINS, WATER HEATER PAN DRAIN, COFFEE MAKER AND OTHER |
| | DEVICES THAT ARE NOT DESIGNED TO RECEIVE F.O.G |
| | DISCHARGES ARE GOING TO THE SANITARY AND NOT TO THE |
| | GREASE WASTE. PLEASE CLARIFY YOUR DRAWING TO SHOW THE |
| | SEPARATION OF GREASE WASTE AND SANITARY WASTE. |
| | |
| | 2. PAGGE P-08 - 2020 FPC 607.1.1 - PLEASE SHOW |
| | COMPLIANCE WITH THE LIMITING FOR HOT WATER DELIVERY. |
| | THE THERMOSTAT ON THE WATER CANNOT SERVE AS THE |
| | LIMITING MEANS FOR HOT OR TEMPERED WATER. A MIXING |
| | DEVICE IS REQUIRED FOR THIS SECTION AND IS IN ADDITION |
| | TO THE LIMITING DEVICE REQUIRED FOR TEMPERED PUBLIC |
| | HANDWASHING. THE DEVICE MUST COMPLY WITH ASSE 1017 AND |
| | MUST BE INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC |
| | 613.1. |
| | |
| | 3. 2017 WPB AMENDS 107.2.1 - THE "AHU CONDENSATE DRAIN |
| | CONNECTION" DETAIL ON PAGE P-08 SAYS "SEE SHEET P1.1 |
| | FOR CONTINUTATION AND P1.1 DOES NOT EXIST. PLEASE |
| | DETAIL THE CONDESATE DRAIN DISPOSAL LOCATION. NOTE: |
| | CONDENSATE CANNOT DISCHARGE TO THE SANITARY. |
| | |
| | 4. 2020 FEC C404.5.1 - PLEASE SHOW THE RECIRCULATING |
| | LINE IN COMPLIANCE WITH THIS SECTION. ACCORDING TO THE |
| | SIZES SHOWN, THE HOT LOOP NEEDS TO BE WITHIN 2 FEET OF |
| | THE PUBLIC LAVS AND 43 FEET OF OTHER FIXTURES. |
| | |
| | 5. 2020 FEC C404.4 INSULATION OF PIPING SHALL BE IN |
| | COMPLIANCE WITH TABLE C403.2.10. PLEASE SHOW DETAILS |
| | FOR PIPING INSULATION. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |