Plan Review Notes
Plan Review Notes For Permit 22090958
Permit Number 22090958
Review Stop P
Sequence Number 1
Notes
Date Text
2022-11-01 12:18:131ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE
 FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE
 WASTE. PLEASE SHOW THAT THE ICE BIN, HAND SINKS, ICE
 BINS, WATER HEATER PAN DRAIN, COFFEE MAKER AND OTHER
 DEVICES THAT ARE NOT DESIGNED TO RECEIVE F.O.G
 DISCHARGES ARE GOING TO THE SANITARY AND NOT TO THE
 GREASE WASTE. PLEASE CLARIFY YOUR DRAWING TO SHOW THE
 SEPARATION OF GREASE WASTE AND SANITARY WASTE.
  
 2. PAGGE P-08 - 2020 FPC 607.1.1 - PLEASE SHOW
 COMPLIANCE WITH THE LIMITING FOR HOT WATER DELIVERY.
 THE THERMOSTAT ON THE WATER CANNOT SERVE AS THE
 LIMITING MEANS FOR HOT OR TEMPERED WATER. A MIXING
 DEVICE IS REQUIRED FOR THIS SECTION AND IS IN ADDITION
 TO THE LIMITING DEVICE REQUIRED FOR TEMPERED PUBLIC
 HANDWASHING. THE DEVICE MUST COMPLY WITH ASSE 1017 AND
 MUST BE INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC
 613.1.
  
 3. 2017 WPB AMENDS 107.2.1 - THE "AHU CONDENSATE DRAIN
 CONNECTION" DETAIL ON PAGE P-08 SAYS "SEE SHEET P1.1
 FOR CONTINUTATION AND P1.1 DOES NOT EXIST. PLEASE
 DETAIL THE CONDESATE DRAIN DISPOSAL LOCATION. NOTE:
 CONDENSATE CANNOT DISCHARGE TO THE SANITARY.
  
 4. 2020 FEC C404.5.1 - PLEASE SHOW THE RECIRCULATING
 LINE IN COMPLIANCE WITH THIS SECTION. ACCORDING TO THE
 SIZES SHOWN, THE HOT LOOP NEEDS TO BE WITHIN 2 FEET OF
 THE PUBLIC LAVS AND 43 FEET OF OTHER FIXTURES.
  
 5. 2020 FEC C404.4 INSULATION OF PIPING SHALL BE IN
 COMPLIANCE WITH TABLE C403.2.10. PLEASE SHOW DETAILS
 FOR PIPING INSULATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved