| Plan Review Notes For Permit 22090958 |
| Permit Number |
22090958 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-24 16:13:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET A 02 - THERE IS AN INDICATION OF AN EXIT FROM | | | THE KITCHEN INTO A PARKING GARAGE; HOWEVER, THERE IS NO | | | INDICATION FO THE TRAVEL DISTANCE NOT TRAVEL PATH FROM | | | THE EXIT DOOR THROUGH THE PARKING GARAGE. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THETRAVEL PATH | | | & TRAVEL DISTANCE PER NFPA 101, CH 12 & CH 7 MEANS OF | | | EGRESS, TO A PUBLIC WAY. | | | | | | | | | | | | 2) SHEETS A 02 & A 03 - THERE ARE NO INDICATIONS OF 3 | | | DOOR #'S ON THE FLOOR PLAN CORRESPONDING TO THE DOOR | | | SCHEDULE. | | | | | | THOUGH THEY MAY BE EXISTING THEY NEED TO ID'D ON THE | | | DOOR SCHEDULE SHOWING COMPLIANCE WITH THE REQUIRED EXIT | | | LOCK/LATCH/HARDWARE PER NFPA 101, CH 12 & CH 7 MEANS OF | | | EGRESS. | | | | | | PLEASE EPROVIDE THE REQUIRED DETAILS. | | | | | | | | | | | | 3) SHEET FS 0 & 1 - THE HOOD AND FIRE SUPPRESSION | | | SYSTEMS SHALL BE SUBMITTED UNDER SEPARATE PEMITST AND | | | SHOP DRAWINGS PER NFPA 96 & 17A | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT & COMPLIANCE. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|