Plan Review Notes
Plan Review Notes For Permit 22090958
Permit Number 22090958
Review Stop E
Sequence Number 1
Notes
Date Text
2022-11-17 12:40:41ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL ALL RECEPTACLES IN KITCHEN AND BAR
 AREA AS GFI PROTECTED AS PER NEC 210.8 (B)(2) KITCHENS
 AND 210.8(B)(5) SINKS. PROVISIONS FOR NEC 210.8(B)(5)
 STATE,
 (B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE
 RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50
 AMPERES OR LESS AND THREE PHASE RECEPTACLES RATED 150
 VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS INSTALLED
 IN THE FOLLOWING LOCATIONS SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL
  
 ONE OF THE KEY WORDS BEING ALL RECEPTACLES
  
 PROVISIONS FOR NEC 210.8(B)(5) SINKS, STATE,
 (5) SINKS ??? WHERE RECEPTACLES ARE INSTALLED WITHIN
 1.8 M (6 FT) FROM THE TOP INSIDE EDGE OF THE BOWL OF
 THE SINK
  
 THE KEY CONCEPT IS 6 FEET. THAT WOULD MEAN EVEN THAT
 THE RECEPTACLES ON THE OUTSIDE OF THE BAR IF THEY ARE
 WITHIN THE 6 FOOT RANGE OF THE SINK
  
 2) PLEASE INSERT A NOTE ON THE ELECTRICAL POWER PLAN
 THAT STATES, ALL VOICE, DATA, SECURITY, FIRE ALARM,
 ACCESS CONTROL, SIGNS, WALK IN COOLERS AND KITCHEN HOOD
 SYSTEM WIRING REQUIRE SEPARATE PERMITS
 3) PLEASE DETAIL THE REQUIRED CLEAR WORKING SPACE IN
 FRONT OF ELECTRICAL PANELS ON ELECTRIC POWER PLAN. NEC
 110.26
 4) AS APPLICABLE, PLEASE DETAIL TAMPER RESISTANT
 RECEPTACLES TO COMPLY WITH NEC 406.12 AS APPLIED TO NEC
 518.2 ASSEMBLY OCCUPANCIES
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  