| 2022-11-17 12:40:41 | ELECTRIC REVIEW FAILED |
| | 1) PLEASE DETAIL ALL RECEPTACLES IN KITCHEN AND BAR |
| | AREA AS GFI PROTECTED AS PER NEC 210.8 (B)(2) KITCHENS |
| | AND 210.8(B)(5) SINKS. PROVISIONS FOR NEC 210.8(B)(5) |
| | STATE, |
| | (B) OTHER THAN DWELLING UNITS. ALL SINGLE-PHASE |
| | RECEPTACLES RATED 150 VOLTS TO GROUND OR LESS, 50 |
| | AMPERES OR LESS AND THREE PHASE RECEPTACLES RATED 150 |
| | VOLTS TO GROUND OR LESS, 100 AMPERES OR LESS INSTALLED |
| | IN THE FOLLOWING LOCATIONS SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL |
| | |
| | ONE OF THE KEY WORDS BEING ALL RECEPTACLES |
| | |
| | PROVISIONS FOR NEC 210.8(B)(5) SINKS, STATE, |
| | (5) SINKS ??? WHERE RECEPTACLES ARE INSTALLED WITHIN |
| | 1.8 M (6 FT) FROM THE TOP INSIDE EDGE OF THE BOWL OF |
| | THE SINK |
| | |
| | THE KEY CONCEPT IS 6 FEET. THAT WOULD MEAN EVEN THAT |
| | THE RECEPTACLES ON THE OUTSIDE OF THE BAR IF THEY ARE |
| | WITHIN THE 6 FOOT RANGE OF THE SINK |
| | |
| | 2) PLEASE INSERT A NOTE ON THE ELECTRICAL POWER PLAN |
| | THAT STATES, ALL VOICE, DATA, SECURITY, FIRE ALARM, |
| | ACCESS CONTROL, SIGNS, WALK IN COOLERS AND KITCHEN HOOD |
| | SYSTEM WIRING REQUIRE SEPARATE PERMITS |
| | 3) PLEASE DETAIL THE REQUIRED CLEAR WORKING SPACE IN |
| | FRONT OF ELECTRICAL PANELS ON ELECTRIC POWER PLAN. NEC |
| | 110.26 |
| | 4) AS APPLICABLE, PLEASE DETAIL TAMPER RESISTANT |
| | RECEPTACLES TO COMPLY WITH NEC 406.12 AS APPLIED TO NEC |
| | 518.2 ASSEMBLY OCCUPANCIES |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |