| Plan Review Notes For Permit 22090922 |
| Permit Number |
22090922 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-01-03 11:20:48 | FBC 109, VALUE IS TO BE MARKET VALUE - WHAT A | | | CONTRACTOR CHARGING FOR MATERIALS, LABOR, OVERHEAD, | | | PROFIT WOULD CHARGE A CUSTOMER FOR THE JOB. | | | | | | | | 2022-12-31 16:40:21 | 3. PLEASE IDENTIFY EACH FBC/NOA NUMBER LOCATION ON | | | FLOOR PLAN. | | 2022-12-31 16:34:19 | 1.PLEASE SUBMIT FBC/NOA DOCUMENTS FOR ALL WINDOWS OR | | | DOORS BEING REPLACED. EXACT UNIT BEING USED MUST BE | | | HIGHLIGHTED/MARKED ON TABLE TO SHOW COMPLIANCE WITH | | | DESIGN PRESSURE REQUIREMENTS. FBC 107.2 2. PLEASE | | | PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO THE PLAN, | | | DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR FBC B | | | 1405.4. |
|