| Plan Review Notes For Permit 22090902 |
| Permit Number |
22090902 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-10-03 17:21:38 | 1ST REVIEW FMC | | | PERMIT: 22090902 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE NEW GENERATOR EXHAUST DOES NOT SHOW LENGTHS. | | | PROVIDE LENGTH OF THE ENTIRE EXHAUST DUCT ALONG WITH | | | THE MAXIMUM DISTANCE ALLOWED BY THE GENERATOR AND | | | MUFFLER. FBC 107.3.5 | | | | | | 2) PROVIDE DETAIL DRAWING FOR THE DIESEL FUEL TANK | | | VENTING. FBC 107.3.5 | | | | | | 3) PROVIDE DETAILS OF SUPPLYING THE COMBUSTION AIR AND | | | CALCULATIONS AS TO THE COMBUSTION AIR REQUIRED FOR THE | | | GENERATOR AND HOW THIS REQUIRED AIR WOULD BE AVAILABLE | | | WITH THE GARAGE DOORS CLOSED. PLEASE ALSO SHOW HOW THE | | | HEAT FROM THE GENERATOR LOCATION WOULD DISSIPATE FBC | | | 107.3.5 | | | | | | 4) SHEET P1.02: THE KEYNOTE 4 CALLED OUT ON THE DRAWING | | | DOES NOT APPEAR IN THE KEYNOTES BOX. PLEASE ADD THE | | | KEYNOTE 4. FBC 107.3.5 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|