Plan Review Notes
Plan Review Notes For Permit 22090902
Permit Number 22090902
Review Stop E
Sequence Number 1
Notes
Date Text
2022-10-11 10:50:14ELECTRIC REVIEW FAILED
  
 1) IT APPEARS SUBMITTAL DOES NOT DETAIL TYPE OF STANDBY
 SYSTEM. PLEASE PROVIDE CLARIFICATION IF THE SYSTEM IS
 TO BE, EMERGENCY, LEGALLY REQUIRED OR OPTIONAL STANDBY
 SYSTEM. ENSURE SYSTEM WILL COMPLY WITH APPROPRIATE
 SYSTEM REQUIREMENTS INCLUDING BUT NOT LIMMETED TO
 SIGNAGE REQUIRED AT ALL SERVICES TO STRUCTURE AND IF
 MERGENCT SYSTEM 700.3(F) TEMPORARY SOURCE OF POWER FOR
 MAINTAINANCE AND REPAIR
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  