| Plan Review Notes For Permit 22090889 |
| Permit Number |
22090889 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-11-02 11:14:06 | 1ST REVIEW FMC | | | PERMIT: 22090889 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE A SCOPE OF WORK FOR THE CHANGES TO THIS | | | DESIGN INCLUDE THE DUCT WORK SIZES. FBC 107.3.5 | | | | | | 2) THE ADDED WINE ROOM CONDENSER LOCATION, IS THIS ON | | | THE EXTERIOR OF THE BUILDING? PROVIDE A DRAWING SHOWING | | | THIS ENTIRE LOCATION INCLUDE HOW THE CONDENSATION FROM | | | THIS UNIT WILL BE DRAINED. FBC 107.3.5 | | | | | | 3) THE NEWLY REVISED DRAWING NOW HAS VENT SHAFTS | | | LABELED, IS THERE ANY WORK AT THESE SHAFTS? | | | | | | 4) PROVIDE THE REQUIRED MAKE-UP AIR FOR THE KITCHEN | | | HOOD EXHAUST. FMC 505.2 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|