2022-09-30 10:11:051) LEASE PROVIDE A MECHANICAL DRAWING THAT CLEARLY
 IDENTIFIES EACH SUPPLY, RETURN AND EXHAUST DUCT AND
 GRILLE. IT APPEARS THIS DRAWING HAS MIXED SHOWING
 SUPPLY FROM THE SAME TRUNK LINE AS RETURNS. FBC 107.3.5
 2) THE EXHAUST OVER THE RANGE IN THE KITCHEN SHOULD
 INCLUDE THE CFM'S THAT THE HOOD MOTOR IS EXHAUSTING
 ALONG WITH A MAKE-UP AIR DETAIL IF THE EXHAUST CFM'S
 REQUIRE IT. FMC 505.1
 3) ADD A NOTE ON THE MECHANICAL DRAWING INDICATING THE
 FUTRE COPPER LINES ARE TO BE CAPPED AND A SEPARATE
 PERMIT WILL BE REQUIRED FOR THIS FUTURE WINE ROOM UNIT.
 ALSO IDENTIFY WHERE THIS FUTURE WINE ROOM WILL BE
 LOCATED. FBC 107.3.5
  