Plan Review Notes
Plan Review Notes For Permit 22090870
Permit Number 22090870
Review Stop P
Sequence Number 1
Notes
Date Text
2022-11-16 11:06:121ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3 - IF REPLACING THE
 PLUMBING AND EQUIPMENT, YOU WOULD NEED TO SHOW IT IS UP
 TO CODE. PLEASE INCLUDE:
 A) THE TDH CALCULATIONS TO GO ALONG WITH THE PUMP CURVE
 B) A PIPING LAYOUT
 C) INCLUDE THE MAIN DRAIN LOCATION LAYOUT - THE ONE
 YOU'VE SHOWN NEEDS TWO WITH ENOUGH DISTANCE BETWEEN
 THEM TO PREVENT ENTRAPMENT
 D) INCLUDE THE VELOCITIES AND PIPE SIZES TO SHOW
 MAXIMUM VELOCITIES ON SUCTION AND PRESSURE PIPING
 E) INCLUDE THE POOL SIZE AND GPM TO SHOW PROPER TURN
 OVER RATE
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  