Plan Review Notes
Plan Review Notes For Permit 22090869
Permit Number 22090869
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-10-12 12:26:33THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEETAND FLAME
 TEST FOR THE FLOOR SOUND UNDERLAYMENT, BUT NO SPEC
 SHEET NOR A PRODUCT NAME FOR THE ACTUAL PROPOSED
 WOOD/ENGINEERED WOOD FLOORING.
  
 ENGINEERED WOOD FLOORING CAN BE MANUFACTURED FROM
 AROUND THE WORLD AND NOT ALL ARE TESTED AND MEETING
 LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE ENGINEERED
 WOOD FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE
 PROPOSED ENGINEERED WOOD FLOORING INDICATING THE FIRE
 BEHAVIOR RATING.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  