Plan Review Notes
Plan Review Notes For Permit 22090869
Permit Number 22090869
Review Stop B
Sequence Number 1
Notes
Date Text
2022-11-16 15:51:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 TEST REPORTS SUBMITTED:
 STC - PROFLEX MSC90, 8" SLAB, QUARRY TILE
 IIC - THE STC TEST REPORT WAS UPLOADED TWICE, ONCE
 NAMED IMPACT SOUND TRANSMISSION
 ASTME-84 - PROFLEX SUPERSIM 90
  
 1. FBC 107, NOT CLEAR WHICH PRODUCT IS PROPOSED. IF
 MSC90 IS PROPOSED, ADVISE HOW YOU HAVE DETERMINED THAT
 THE SLAB IS 8".
  
 IF SUPERSIM 90 IS PROPOSED, PLEASE ADVISE VIA A
 RESUBMITTAL LETTER, THE STC/IIC TEST REPORTS WILL BE
 UPLOADED FOR YOU.
  
 FBC B 1207, FBC B 603.1.
  
  